Product Details:
Payment & Shipping Terms:
|
Usage: | Industrial | Temperature Range: | -200°C - 1820°C Or -392°F - 3308°F |
---|---|---|---|
Thermocouples Stability: | ±0.15% Of Reading Or 0.15°C (0.27 °F) | Input: | 8 Channels 4-20 MA |
Output: | FOUNDATION Fieldbus\Mancheste | Supply Voltage: | 9.0 To 32.0 V Dc; 22ma Maximum |
High Light: | 4-20ma temperature transmitter,Rosemount Temperature transmitter |
High Density Temperature Measuring Instruments Rosemount 848T
Quick Detail:
· High density applications
· Multi-sensor measurement capabilities
· Accuracy:
o ±0.30°C (±0.54°F) for Pt100 RTD
o ±0.70°C (±1.26 °F) for Type J Thermocouple
· Measurement validation diagnostic option
· Approximately 1.5 seconds to read all 8 inputs
· 0–99% non-condensing relative humidity
· Transmitters are tested to high pipeline vibration
Description:
The Rosemount 848T Foundation Fieldbus Temperature Transmitter simplifies and reduces the cost of a plant's process control architecture. It replaces traditional temperature monitoring methods (wired direct, low cost single input transmitters, and multiplexers) with an intrinsically safe, eight input transmitter that mounts close to the process. The industry first Measurement Validation Diagnostic available on the Rosemount 848T Fieldbus transmitter provides insight into your process and can identify measurement abnormalities before they become a major issue, saving your time and money associated with process shutdowns and helping you run your process more efficiently. The 848T also comes with a new Device Dashboard, which gives users a clear view of everything needed to evaluate, diagnose, and configure the 848T. The new interface leverages Human Centered Design principles to create a streamlined, easy and efficient user experience, eliminating the complexities, and allowing the user to realize the benefits of FOUNDATION fieldbus.
Applications:
Specifications:
Key Specifications | |
Digital Accuracy | ±0.30°C (±0.54°F) for Pt100 RTD ±0.70°C (±1.26 °F) for Type J Thermocouple |
Ambient Temperature Effects | 0.003 °C per 1 °C change in ambient temperature for PT100 |
Stability | 0.1% reading or 0.1°C whichever is greater for 2 years for RTD ±0.1% of reading or 0.1°C, whichever is greater for one year for thermocouples |
Input | 8 channels (combination of 2-3 wire RTD’s, thermocouples, millivolts and ohms) 4-20 mA inputs using optional connectors |
Output | FOUNDATION™ fieldbus Manchester-encoded digital signal that conforms to IEC 1158-2 and ISA 50.02 |
Supply Voltage/Current Consumption | 9.0 to 32.0 V dc; 22ma maximum |
Competitive Advantage:
· Four independently configurable RTD, thermocouple, ohm, millivolt and 4 - 20 mA signals
· Lowers installed cost by eliminating long wire runs to the control room
· Dependable performance by enhancing measurement reliability for trustworthy data
· Simplified installation and configuration practices for faster start-ups
· Fully compatible with WirelessHART networks with greater than 99% data reliability
· Eight user configurable alerts for advanced measurement monitoring
· Temperature sensor diagnostics for continuous monitoring of sensor integrity
· Type 4x, IP66 housings allows for installation in harsh process environments
· Best ambient temperature compensation reduces measurement error in harsh applications, especially for wide fluctuations of ambient temperature
Contact Person: Ms. Shouyan Huo
Tel: +86-18600678435
Fax: 86-10-82561707